Documented Canadian cases
These are published accounts of backflow or cross-connection events in Canada. Each note stays with its source. Training material sometimes mentions a 1933 Chicago fair as an early example outside Canada. It is not listed here.
2011 · Oakville, ON
Cleaning chemicals in a high-school water line
Durham Region and the Environmental Operators Certification Program describe a 2011 closure of an Oakville high school after cleaning chemicals entered the school's water lines. Both accounts say a backflow device kept the chemicals from reaching the municipal supply.
- Region of Durham · Backflow Prevention Program
- Environmental Operators Certification Program · Backflow Prevention, Cross Connection Control, and the EOCP
March 2005 · Stratford, ON
Car-wash cleaner in the city system
In March 2005 a car-wash cleaning agent reached Stratford's drinking water through an open valve on a cross-connection. The city advised people not to drink the water. Published accounts say about 30,000 people were affected, 19 sought medical attention, and the business was later fined $75,000. The supply was affected for several days.
- American Water Works Association, Canadian section · AWWA Canadian Cross-Connection Control Manual, Chapter 2, p. 2.2
- Region of Durham · Backflow Prevention Program
- City of Toronto / Walkerton Clean Water Centre · Standard of Care training materials, Stratford case study
2002 · Edmonton, AB
Fire-system water stayed inside one building
After a water-main break in 2002, brackish water from a building's fire-protection piping moved into that building when a single check valve failed. The AWWA Canadian manual says the water did not enter the city main and that no residents were reported ill.
- American Water Works Association, Canadian section · AWWA Canadian Cross-Connection Control Manual, Chapter 2, p. 2.2
September 1998 · Regina, SK
Air from an irrigation blow-out
In September 1998 Regina received a complaint about discoloured water and air in the lines. The AWWA Canadian manual says crews had been blowing out irrigation lines at Rick Hansen Park, and a 4-inch isolation valve was not fully closed or seated, so air reached customers through the supply piping.
- American Water Works Association, Canadian section · AWWA Canadian Cross-Connection Control Manual, Chapter 2, p. 2.2
1997 · Guelph, ON
Petroleum-plant chemicals in the city mains
In 1997 chemicals from a petroleum plant entered Guelph's water mains after a chemical injection system and its backflow preventer failed. About 50,000 people in the northern half of the city were told not to drink the water for several days while the mains were flushed. Litigation related to the event concluded in 2010.
- American Water Works Association, Canadian section · AWWA Canadian Cross-Connection Control Manual, Chapter 2, p. 2.2
- Region of Durham · Backflow Prevention Program
1989 · Edmonton, AB
Laboratory nutrient in a building's hot water
The Environmental Operators Certification Program reports that in 1989 staff at an Edmonton research facility noticed an odour in the hot water. A growth nutrient from the laboratory had moved into the building's domestic hot-water system. The building's potable piping was chlorinated and flushed.
- Environmental Operators Certification Program · Backflow Prevention, Cross Connection Control, and the EOCP